UTICAJ ZASIĆENJA STRUJNIH TRANSFORMATORA NA RAD DIFERENCIJALNE ZAŠTITE TRANSFORMATORA SOPSTVENE POTROŠNJE U HE „ĐERDAP 1”

Fleksibilnost elektroenergetskog sistema / Zbornik CIGRE (2023).  (str 847- 858)

AUTOR(I) / AUTHOR(S): Nikola Sučević, Saša Gligorov, Petar Nikolić

E-ADRESA / E-MAIL: nikola.sucevic@ieent.org

Download Full Pdf   

DOI:  10.46793/CIGRE36.0847S

SAŽETAK / ABSTRACT:

U ovom radu izvršena je analiza rada diferencijalne zaštite transformatora sopstvene potrošnje bloka 2 hidroelektrane HE „Đerdap 1” pri pojavi kvara van zone štićenja, uvažavajući uticaj pojave zasićenja strujnih transformatora i algoritma rada zaštitnog uređaja. Pri kratkim spojevima u sistemu koji rezultuju strujama visokog intenziteta, može doći do pojave izobličenja talasnog oblika struja na sekundaru strujnih transformatora, što može da utiče na rad sistema zaštite. Analize su vršene na softverskom modelu zaštitnog uređaja i na stvarnom uređaju, injektiranjem struja u zaštitni uređaj primenom ispitnog kofera. Izvršeno je poređene odziva softverskog modela zaštitnog uređaja i stvarnog uređaja. Modelovanje mreže i analize vršene su u softverskom paketu DlgSILENT PowerFactory, a za ispitivanje rada zaštitnog uređaja korišćen je DOBLE ispitni kofer.

KLJUČNE REČI / KEYWORDS:

zasićenje strujnih mernih transformatora za zaštitu, diferencijalna zaštita transformatora

LITERATURA / REFERENCES:

  • R.E. Cosse, D.G. Dunn, R.M. Spiewak, CT Saturation Calculations – Are They Applicacable in the Modern World? – Part I, The Question, Petroleum and Chemical Industry Conference, 2005
  • R.E. Cosse, D.G. Dunn, R.M. Spiewak, Stanley E. Zocholl, Terence Hazel, David T. Rollay, CT Saturation Calculations – Are They Applicacable in the Modern World? – Part II, Proposed Responsabilities, Petroleum and Chemical Industry Technical Conference, 2007. PCIC ’07. IEEE
  • Kasztenny, J. Mazereeuw, and H. DoCarmo, „CT Saturation in Industrial Applications – Analysis and Application Guidelines,“ in Proc. the 60th Annual Conference for Protective Relay Engineers, March 27-29, 2007
  • IEC 60044-1, Instrument transformers – Part 1: Current transformers, International Electrotechnical Commission
  • IEC 60044-6, Instrument transformers – Part 6: Requirements for protective current transformers for transient performance, International Electrotechnical Commission
  • C57.13-2007 IEEE Standard requirements for Instrumental Transformers, IEEE Power Engineering Society
  • C37.110-2007 IEEE Guide for the Application of Current Transformers Used for Protective Relaying Purposes, IEEE Power Engineering Society
  • DIgSILENT PowerFactory, www.digsilent.com
  • Current Transformer (StaCT), Technical Reference Documentation, DIgSILENT PowerFactory 2017
  • Transformer Differential Protection / 7UT6, SIPROTEC 4 7UT6 differential protection relay for transformers, generators, motors and busbars, Siemens SIP Edition No. 7
  • SIPROTEC 4, 7UT6x, Manual C53000-G1176-C230-5, Edition 09.2016
  • DIgSILENT PowerFactory, Relay Model Description ,Siemens 7UT6xx, Version 002, Technical Reference Documentation
  • Doble Engineering Company, https://www.doble.com/
  • TransWin 3.3, User’s Guide, Doble Engineering Company
  • DIGSI 4, Operation Software for SIPROTEC 4, SIPROTEC Compact, SIPROTEC 3 and SIPROTEC 2 protection devices