37. саветовање CIGRE Србија (2025) СИГУРНОСТ, СТАБИЛНОСТ, ПОУЗДАНОСТ И RESILIENCE ЕЛЕКТРОЕНЕРГЕТСКОГ СИСТЕМА МУЛТИСЕКТОРСКО ПОВЕЗИВАЊЕ У ЕНЕРГЕТИЦИ И ПРИВРЕДИ – A3.03
АУТОР(И) / AUTHOR(S): Jovan Mikulović, Milenko Jovanović, Tomislav Rajić
DOI: 10.46793/CIGRE37.A3.03
САЖЕТАК / ABSTRACT:
In electric arc furnace plants, transformers are exposed to the risk of switching overvoltages that occur during the disconnection of vacuum circuit breakers, particularly due to multiple contact flashovers. To protect transformers, RC filters are employed to suppress high-frequency overvoltages. This paper presents a procedure for determining the parameters of the RC filter based on technical data and simulations, as well as the verification of their effectiveness through the analysis of transient phenomena and steady-state behavior. Additionally, the effects of overvoltages during the transient period are analyzed, as well as the conditions that the RC filter must meet to ensure reliable protection of the transformer under real operating conditions.
КЉУЧНЕ РЕЧИ / KEYWORDS:
transformers, electric arc furnaces, RC filter
ПРОЈЕКАТ / ACKNOWLEDGEMENT:
ЛИТЕРАТУРА / REFERENCES:
- M. Savic, Visokonaponska oprema, Akademska misao, Beograd 2004.
- M. Đurić, V. Ilić, Visokonaponska razvodna postrojenja, AGM Knjiga, Beograd 2017.
- J. Nahman, V. Mijailović, Razvodna postrojenja – drugo izdanje, Akademska misao, Beograd 2015.
- ABB Technical standard 1ZIT 5680–101, Sistemi di protezione dalle sovratensioni durante i transitori di manovra
- R. Faranda, M. Giussani, G. Testin, RC filter to protect industrial arc furnace transformers during switching–off, Proceedings of the 2nd IASME / WSEAS International Conference on Energy & Environment (EE’07), Portoroz, Slovenia, May 15-17, 2007