PRAĆENJE STANJA NAPONA VRATILA U REVITALIZOVANIM GENERATORIMA U HE “ĐERDAP 1“

37. саветовање CIGRE Србија (2025) СИГУРНОСТ, СТАБИЛНОСТ, ПОУЗДАНОСТ И RESILIENCE ЕЛЕКТРОЕНЕРГЕТСКОГ СИСТЕМА МУЛТИСЕКТОРСКО ПОВЕЗИВАЊЕ У ЕНЕРГЕТИЦИ И ПРИВРЕДИ – A1.06 

АУТОР(И) / AUTHOR(S): Милан Мишић, Драган Николић, Милош Гицић, Драган Глувачевић, Жарко Несторовић, Драган Белонић, Петар Николић

Download Full Pdf   

DOI:  10.46793/CIGRE37.A1.06

САЖЕТАК / ABSTRACT:

Six hydropower units at the Đerdap 1 HPP have begun a new operating life after the revitalization. The revitalized units are equipped with modern devices for monitoring the operating condition in order to reduce the risk of outages, reduce maintenance costs and extend the service life of the equipment. In addition, the power plant staff periodically conducts additional measurements and analyses on individual assemblies and parts of the equipment in order to promptly detect deviations of certain parameters from the values that are common for the plant. One of the parameters that is periodically measured is the induced voltage on the shaft of the hydropower unit. This paper presents the results of shaft potential measurements in the previous period. The conclusions and measurements presented in this paper can help in understanding the occurrence of bearing currents and the necessary measures to reduce negative impacts on bearings as well as other irregularities in the operation of the hydropower unit.

КЉУЧНЕ РЕЧИ / KEYWORDS:

synchronous generator, induced shaft voltage, bearing currents

 ПРОЈЕКАТ /ACKNOWLEDGEMENT :

ЛИТЕРАТУРА / REFERENCES:

  • P.L. Alger, H.W. Samson, Shaft currents in electric machines. Journal Am. Inst. Electr. Eng. 1923, 42, 1325–1334.
  • J. M. Gruber, E. F. Hansen, Electrostatic shaft voltage on steam-turbine rotors. Journal of Engineering for Power, (1959), 81(1), 97-106.
  • K.B. Tawfiq, M. Güleç, P. Sergeant, Bearing Current and Shaft Voltage in Electrical Machines: A Comprehensive Research Review. Machines 2023, 11, 550.
  • I. Klasnić, D. Joksimović, Z. Ćirić, Potencijal vratila kod turboagregata, Zbornik radova, Elektrotehnički institut Nikola Tesla, Vol. 26 (2016), 129-139.
  • IEEE Standard Test Procedure for Polyphase Induction Motors and Generators, IEEE Std 112™-2004.
  • IEEE Guide for Online Monitoring of Large Synchronous Generators (10 MVA and Above), IEEE Std 1129™-2014.
  • G. Perović, S. Ninković, H. Moritz, Least Squares: (monograph): with 87 figures and 90 tables. 2005.